Technology of Electrical Automatic

BATTERY SUPERVISE SYSTEM

The BMS monitoring system monitor and signalise deep battery discharge in real time, eventually discharging of particular cells of battery sets, measured voltage on particular cells of battery sets, over discharging or overcharging battery current, battery temperature deviation from specified values and etc. Overrun of every of mentioned parameters could lead to battery set destruction, so it is needed to have immediate information about battery status.

The system si design into 19″ rack high 2U and can be built into 19″ cabinet or can be fixed on the wall in vertical position. Method of fixation has to be specified ba client in advance.

Battery monitoring system is fully autonomy working or can be directly battery-powered. So it is not necessary to provide power supply from back-up distribution mains, what enable to situate battery-monitoring system directly into accumulators` installation or storage room.

Features

-. Complex modular supervisory system of battery status, resistance, battery temperature and voltage monitoring for comprehensive battery state of health analysis;
-. Maximum monitor 6 independent battery strings, or 360pcs battery cell;
-. LCD display with characters;
-. Fully programmable measuring process, communication via RS485, Ethernet port
galvanic isolation of measurement;
-. Build into 19” cabinet eventually to place it on the wall

Monitoring system HB operation is suitable for applications where is required monitoring of battery operation.

The BMS monitoring system monitor and signalise deep battery discharge in real time, eventually discharging of particular cells of battery sets, measured voltage on particular cells of battery sets, over discharging or overcharging battery current, battery temperature deviation from specified values and etc. Overrun of every of mentioned parameters could lead to battery set destruction, so it is needed to have immediate information about battery status.

The system si design into 19″ rack high 2U and can be built into 19″ cabinet or can be fixed on the wall in vertical position. Method of fixation has to be specified ba client in advance.

Battery monitoring system is fully autonomy working or can be directly battery-powered. So it is not necessary to provide power supply from back-up distribution mains, what enable to situate battery-monitoring system directly into accumulators` installation or storage room.

Technical parameters

Technical specification of the system

System maximal voltage                                  20~800 V DC ±0.5%; 0.1V
System maximal Current                                 0~1000A ±1%(Fullscale), 0.1A
Number of measured battery string               Max. 6
Number of measured cells                              Max. 360 cells 

Technical specification of module

Battery voltage measuring range                   0 ~ 16 V DC (1.2V/2V/6V/12V)±0.1%; 0.001V
Internal resistance                                          50~65535uohm, ±2%, 1uohm