Free cookie consent management tool by TermsFeed Update cookies preferences
Technology of Electrical Automatic

GYDCG-UB1K-ARH Isolation Monitoring Device

GYDCG-UB1K-ARH Isolation Monitoring Device

The GYDCG-UB1K-ARH Isolation Monitoring Device is based on the non-balanced bridge principle, integrating monitoring and protection functions. It can monitor the insulation resistance of DC floating systems within 0Ω to 10MΩ. and detect DC voltage within 0V to 1000V.

This Isolation Monitoring Device is equipped with a high-voltage grounding switch, enabling online on-off functionality. The DC-to-ground high-voltage test does not exceed 4200Vdc. It has RS485 communication to remote get values and set alarm resistance thresholds by DIP switches. Furthermore, users can choose between passive reset and automatic reset through DIP switch configurations, and the module stops operating during manual or remote reset.

Category:

The GYDCG-UB1K-ARH Isolation Monitoring Device is based on the non-balanced bridge principle, integrating monitoring and protection functions. It can monitor the insulation resistance of DC floating systems within 0Ω to 10MΩ. and detect DC voltage within 0V to 1000V.

This Isolation Monitoring Device is equipped with a high-voltage grounding switch, enabling online on-off functionality. The DC-to-ground high-voltage test does not exceed 4200Vdc. It has RS485 communication to remote get values and set alarm resistance thresholds by DIP switches. Furthermore, users can choose between passive reset and automatic reset through DIP switch configurations, and the module stops operating during manual or remote reset.

Category:

Features

  • High voltage grounding switch
  • Power supply: 10-30VDC
  • Widely insulation monitoring range (100V~1000VDC)
  • Insulation monitoring equipment self-test
  • Adaptive capacitance to ground
  • Convenient parameter setting
  • Remote monitoring and management
  • Monitor positive and negative poles
  • Ground insulation resistance
  • Voltage reverse polarity alarm
  • Rail mounting or screw fixing

 

Specifications

Parameter Value
Power supply 10-30VDC, Power 3w
DC voltage range 100V~1000V
DC voltage

measurement accuracy

≤2V+0.3%
Insulation resistance

measurement range

1KΩ~10 MΩ

(DC System voltage:100V~1000V)

Insulation monitoring accuracy

((When :DC voltage:100V-1000V)

CY range Resistance range Accuracy
0~0.8μF ≤60kΩ ≤3kΩ
60kΩ<R≤1MΩ ≤5%
0.8μF ~3μF ≤60kΩ ≤6kΩ
60kΩ<R≤1MΩ ≤20%
Off-line pressure test <2mA
Maximum relay switching voltage 250VAC/30VDC
Maximum relay switching current 3A
Relay contact resistance <100mΩ
Relay insulation resistance 100MΩ
Standard IEC 61851-23 (2014-03):2014-11
Humidity 85%
Storage temperature – 40°C ~125°C
Operating temperature – 40°C ~75°C

 

Pressure point Maximum voltage rating Time
DC+/DC- To GND 4200VDC/2500VAC ≤1min
Power supply +/- To GND 3500VDC/2500VAC ≤1min
RS485 A/B To GND 3500VDC/2500VAC ≤1min
DC+/DC- To Power supply +/- 3500VDC/2000VAC ≤1min
DC+/DC- To A/B 3500VDC/2000VAC ≤1min

Typical wiring

 

 

Dimension

 

Downloads

Brochure of IMD-SERIES-DC-INSULATION-MONITORING-DEVICES

GYDCG-UB1K-ARH -User manual- V1.0

GYDCG-UB1K-ARH -User manual- V1.11

Releted Articles

» What Is Insulation Monitoring Device?

» Insulation Resistance Monitoring And Measuring

» What Is The DC Insulation Monitoring Device Working Principle?

» Insulation Monitoring for DC Charging Stations