Specification
Electrical Signal Inputs of QPPX Programmable Transducer:
Nominal input |
1 or 5 Amp C.T. connected |
110V, 230V, 240V, 400V, 415V ac +/-20% |
Power consumption |
<1 VA voltage |
<0.2 VA current |
Overload capacity |
1.2 times continuous |
5sec @ 10 times of rated current
2sec @ 2 times of rated voltage |
Frequency range |
40~65Hz |
Measurment Output:
Standard outputs |
4~20mA/ 0-20mA programmable
(0~5V / 0~10V optional) |
Maximum load |
<390 Ω (current output)
>10KΩ (voltage output) |
Ripple |
<1% peak to peak |
Response time |
<350ms 0-90% |
<500ms 0-99% |
Measurment Accuracy of QPPX Programmable Transducer:
Class |
0.2% / 0.5 complying with IEC 60688 |
Accurate range |
0 – 120% I |
Frequency influence |
<0.05% per Hz |
Load influence |
<0.25% of F.S. for specific load range |
Auxiliary Supply of QPPX Programmable Transducer:
Rating |
85-265Vac/dc,
Optional 12V, 24V, 48VDC |
Consumption |
<3VA |
Galvanic isolation between I/O and AUX:
Test voltage |
2KV RMS 50Hz for 1 minute |
impulse |
4KV 1.2/50µsec waveform |
Temperature requirements of QPPX Programmable Transducer:
Operating |
-10~55C |
Storage |
-40~70C, 20 ~ 93%RH ; Noncondensing |