The PR200 Digital Motor Protection Relay monitors 3-phase power lines for abnormalities. This 3-phase motor protection relay can be used with motors less than 690V/820A. It can be packed inside a small and economical package so this motor protection relay can save you time and money.
Startup mode: protected mode
Protection functions: overload, phase failure, blockage, unbalance, timeout, underload, leakage, Undervoltage, overvoltage
Relay output: programmable 1-2 channels of DO
Display mode: LED display
Measurement parameters: 3I, 3U
Features
- High accuracy sample calculation, class 0.5 for 2% -120% measurement range; class 1 for 120% -1000% measurement range.
- Built-in 2-channel relay
- You can set protected trip mode, alarm mode, and trig mode
- Channel 1 relay can be used for alarm in protection mode
- Channel 2 relay can be used for trig operation in protection mode
- You can set each protection function to act off, alarm, or trip
- Includes Sequence of Event function that can log the last 10 trip records
- Programmable analog output function
- You can choose the RS-485 communication interface.
- Programmable analog output function and RS-485 communication interface are available for user selection.
- Can provide basic electrical parameters for user SCADA system.
- Wide range of power supply AC85-265V or AC80-450V.
Specifications
The working environment of PR200 Motor Protection Relay:
Motor rated voltage |
AC380V / AC660V |
Motor rated current |
0.5-820A |
Working temperature |
-20C ~ +60C |
Storage temperature |
-40C ~ +80C |
Relative humidity |
< 93% RH |
Elevation |
not more than 3000 m |
Atmospheric conditions |
installation site does not allow the explosive medium, containing gas to corrode metal and damage the insulation and conductive medium. |
Measuring the Accuracy of PR200 Motor Protection Relay:
Current |
± 0.5% (2% to 120% of Ie) |
± 1% (120% to 10% of Ie) |
Voltage |
± 0.5% |
Leakage current |
± 1% (10% to 100% of Ir) |
Analog Output |
± 1% (4 ~ 20mA) |
Electrical parameters:
Auxiliary Power |
AC80-450V (DC110V-500V) |
Power consumption |
<4 VA |
Insulation resistance |
> 100MΩ |
Relay |
Trip relay @ 10A / AC250V, 10A / 30VDC (NC node) |
Alarm relay @ 5A / 250VAC, 5A / 30VDC (NO node) |
Electrical test of PR200 Motor Protection Relay:
IEC 61000-4-2 |
level III |
IEC 61000-4-4 |
level III |
IEC 61000-4-5 |
level III |
IEC 61010-1 |
AC2kV/1min Between power / input / output |
Selectable Models
Products code |
IEEE
/ ANSI
C37.2
|
PR201 |
PR202 |
PR203 |
PR240 |
PR260 |
PR265 |
PR26C |
PROTECTION FUNCTION |
Max. Start Time |
48 |
● |
● |
● |
● |
● |
– |
– |
Overload |
49, 51 |
● |
● |
● |
● |
● |
– |
– |
Increased safety motors overload |
51 |
– |
– |
– |
● |
● |
– |
– |
Over
Current – Jam in starting |
51R |
● |
● |
● |
● |
● |
– |
– |
Over Current – Jam in running |
51R |
– |
● |
● |
● |
● |
– |
– |
Phase loss |
47 |
● |
● |
● |
● |
● |
– |
– |
Current imbalance |
46 |
● |
● |
● |
● |
● |
– |
– |
Over voltage |
59 |
– |
● |
● |
● |
● |
– |
– |
Undervoltage |
27 |
– |
● |
● |
● |
● |
– |
– |
Under Power |
32L |
– |
● |
● |
● |
● |
– |
– |
Ground fault |
50G/N,
51G/N |
– |
○ |
○ |
● |
● |
– |
– |
Over Current – Short |
50 |
– |
– |
– |
● |
● |
– |
– |
Over temperature |
38 |
– |
– |
– |
○ |
○ |
– |
– |
Abnormal frequency |
81U/81O |
– |
– |
– |
● |
● |
– |
– |
Lead/ Lag PF / Low Power Factor |
55 |
– |
– |
– |
● |
● |
– |
– |
Welded Contactor |
74 |
– |
– |
– |
● |
● |
– |
– |
External fault |
86
or 94 |
– |
– |
– |
– |
● |
– |
– |
Internal failure |
3 |
– |
– |
– |
– |
● |
– |
– |
Restart |
|
– |
– |
– |
● |
● |
– |
– |