Technology of Electrical Automatic

DCEM-3MS (BJ-195-3PS) DC Energy Meter With RS485

DCEM-3MS (BJ-195-3PS) DC Energy Meter With RS485

BJ-195-3PS  DC Energy Meter With RS485 is a combined DC power measurement terminal, which is a highly integrated product for DC parameter measurement applications. It can accurately measure 1 DC voltage and 1 DC current (with direction) with an external shunt, power, total electricity, each single-way electricity, and other electrical parameters, and can be equipped with a switch output.

This Multifunction DC energy meter has an RS485 interface, supports the MODBUS-RTU communication protocol, and can upload the data collected by the measurement and the status of the equipment. The device can be widely used in electric power, communication, railway, transportation, environmental protection, petrochemical, steel, and other industries to monitor the current and power consumption of DC equipment.

Category:

BJ-195-3PS  DC Energy Meter With RS485 is a combined DC power measurement terminal, which is a highly integrated product for DC parameter measurement applications. It can accurately measure 1 DC voltage and 1 DC current (with direction) with an external shunt, power, total electricity, each single-way electricity, and other electrical parameters, and can be equipped with a switch output.

This Multifunction DC energy meter has an RS485 interface, supports the MODBUS-RTU communication protocol, and can upload the data collected by the measurement and the status of the equipment. The device can be widely used in electric power, communication, railway, transportation, environmental protection, petrochemical, steel, and other industries to monitor the current and power consumption of DC equipment.

Category:

Features

  • High precision measurement
  • Small size, easy installation
  • Standard 35mm rail installation
  • High security: high isolation voltage
  • Single-phase wiring
  • way independent shunt access, segment LCD display
  • Powerful data acquisition and processing functions
  • A variety of anti-interference measures, high security
  • LCD screen display intuitive, easy to operate

Specification

Voltage  input
Rated value 0-1000V
Maximum voltage display 0-9999V
Overload Measurement: 1.2 times Instantaneous: 2 times/10s
Impedance >1 kΩ/V
Accuracy Accuracy grade: 0.5%FS
Current  input
Rated value Shunt: conventional 75mV, others need to be specified separately
Maximum current display 0-9999A
Overload Measurement: 1.2 times Instantaneous: 10 times/1s
Impedance <100mΩ
Accuracy Accuracy grade: 0.5%FS
Power supply
The scope of work AC/DC85V~265V
Power consumption ≤4VA
Output
Digital interface RS-485,MODBUS-RTU
Pulse output Optional 1 channel active energy pulse output
Environment
Working environment -25~55℃,Altitude ≤2000m, 98%RH, no condensation, no corrosive gas
Storage environment -30~75℃
Safety
Pressure resistance Input and Power>2kV; Input and Output>2kV; Power and Output>2kV
Insulation Input, output, power supply > 5MΩ to the chassis
Others
Electric energy Active energy level 1
Display LCD with white backlit
Power Accuracy: 0.5%FS

Dimension & Wiring

Dimension of  DC Energy Meter

 

Wiring Method of DC Energy Meter

Downloads

Brochure of DCEM-SERIES-DC-ENERGY-METER

BJ-195-3PS-DC-Energy-Meter-User-Manual-V1.10

» What Is DC Energy Meter?

» DC Energy Meter For EV Charger – Applications And Advantages

» DC Energy Meter For Solar System – Applications And Advantages

» What Is The Difference Between AC Energy Meter And DC Energy Meter?