Specifications
| Parameter |
Value |
| Power supply |
9-30VDC, Power 3W |
| DC voltage range |
100V~1000V |
| DC voltage
measurement accuracy |
100-200Vdc: ≤2V |
| 200-1000Vdc: ≤0.5% |
| Insulation resistance
measurement range |
1KΩ~10 MΩ
(DC system voltage:100V~1000V) |
| Insulation monitoring accuracy
@DC system voltage:100V-1000V) |
CY range |
Resistance range |
Accuracy |
| 0~0.8μF |
≤60kΩ |
≤3kΩ |
| 60kΩ<R≤1MΩ |
≤5% |
| 0.8μF ~3μF |
≤60kΩ |
≤6kΩ |
| 60kΩ<R≤1MΩ |
≤20% |
| Off-line withstand test |
<2mA |
| Maximum relay switching
current /voltage |
4A@400Vac/ 600Vdc |
| Relay contact resistance |
<100mΩ |
| Relay insulation resistance |
1000MΩ |
| Standard |
IEC 61851-23 (2014-03):2014-11 |
| Storage environment |
Temp: – 55°C ~90°C, Humidity: ≤90%RH, Altitude: ≤3500m |
| Operating environment |
Temp: – 40°C ~75°C, Humidity: ≤90%RH, Altitude: ≤3500m |
High voltage test
| Voltage test point |
Maximum voltage rating |
Time |
| DC+/DC- to GND |
4200VDC/3000VAC |
≤1min |
| Power supply +/- to GND |
3500VDC/2500VAC |
≤1min |
| RS485 A/B to GND |
3500VDC/2500VAC |
≤1min |
| DC+/DC- to power supply +/- |
4200VDC/3000VAC |
≤1min |
| DC+/DC- to A/B |
4200VDC/3000VAC |
≤1min |
Note:
The power supply (+/-), RS485(A/B), and Ground(G) should be isolated from each other.