GYDCG-UBCW2K-Series IMD Insulation Monitoring Device

GYDCG-UBCW2K-Series IMD Insulation Monitoring Device

GYDCG-UBCW2K series IMD Insulation Monitoring Device can monitor the insulation resistance value of the positive and negative poles of the DC floating system to ground from 0Ω to 10MΩ, and can also detect the DC voltage value from 0V to 2000V. 3 Functions are optional: without communication, alarm dry contact output; with communication only; with communication alarm dry contact output.

Insulation resistance monitoring can only be realized when the DC voltage is between 100V and 2000V. When the DC voltage is less than 100V, or the insulation monitoring is not enabled, the insulation resistance read is 65535 (invalid number). When the measured value is greater than 10MΩ, the value received by the communication is 60000 (infinity).

Category:

GYDCG-UBCW2K series IMD Insulation Monitoring Device can monitor the insulation resistance value of the positive and negative poles of the DC floating system to ground from 0Ω to 10MΩ, and can also detect the DC voltage value from 0V to 2000V. 3 Functions are optional: without communication, alarm dry contact output; with communication only; with communication alarm dry contact output.

Insulation resistance monitoring can only be realized when the DC voltage is between 100V and 2000V. When the DC voltage is less than 100V, or the insulation monitoring is not enabled, the insulation resistance read is 65535 (invalid number). When the measured value is greater than 10MΩ, the value received by the communication is 60000 (infinity).

Category:

Features

  • Advanced Insulation Monitoring (High Voltage )
  • Adaptive Ground Capacitance Detection
  • Insulation resistance from 0Ω to 10MΩ
  • DC voltage from 0V to 2000V
  • RS485 Control and Data Reading
  • LD1 & LD2 LED Indicators
  • Fast Response within 1s
  • Reliable Relay Output

Specifications

Parameter Value
Power supply 10-30VDC, Power 3w
DC voltage range 0V~2000V
DC voltage

measurement accuracy

≤2V+0.3%
Insulation resistance

measurement range

1KΩ~10 MΩ

(DC System voltage:100V~2000V)

Insulation monitoring

accuracy

DC voltage:100V-300V ≤3kΩ+10%
DC voltage:300V-2000V ≤3kΩ+5%
CY>0.3μF, insulation resistance>1MΩ or CY>1μF >10%
Off-line pressure test <2mA
Maximum relay switching voltage 250VAC/30VDC
Maximum relay switching current 3A
Relay contact resistance <100mΩ
Relay insulation resistance 100MΩ
Standard IEC 61851-23 (2014-03):2014-11
Humidity 85%
Storage temperature – 40°C ~125°C
Operating temperature – 40°C ~75°C

Typical wiring

Dimension

 

Downloads

Brochure of IMD-SERIES-DC-INSULATION-MONITORING-DEVICES